| upsIdentManufacturer | 
      .1.3.6.1.2.1.33.1.1.1 | 
    
    
      | 
        The name of the UPS manufacturer.
       | 
    
    
      | upsIdentModel | 
      .1.3.6.1.2.1.33.1.1.2 | 
    
    
      | 
        The UPS Model designation.
       | 
    
    
      | upsIdentUPSSoftwareVersion | 
      .1.3.6.1.2.1.33.1.1.3 | 
    
    
      | 
        The UPS firmware/software version(s).  This variable
        may or may not have the same value as
        upsIdentAgentSoftwareVersion in some implementations.
       | 
    
    
      | upsIdentAgentSoftwareVersion | 
      .1.3.6.1.2.1.33.1.1.4 | 
    
    
      | 
        The UPS agent software version.  This variable may or
        may not have the same value as
        upsIdentUPSSoftwareVersion in some implementations.
       | 
    
    
      | upsIdentName | 
      .1.3.6.1.2.1.33.1.1.5 | 
    
    
      | 
        A string identifying the UPS.  This object should be
        set by the administrator.
       | 
    
    
      | upsIdentAttachedDevices | 
      .1.3.6.1.2.1.33.1.1.6 | 
    
    
      | 
        A string identifying the devices attached to the
        output(s) of the UPS.  This object should be set by
        the administrator.
       | 
    
    
      | upsBatteryStatus | 
      .1.3.6.1.2.1.33.1.2.1 | 
    
    
      | 
        The indication of the capacity remaining in the UPS
        system's batteries.   A value of batteryNormal
        indicates that the remaining run-time is greater than
        upsConfigLowBattTime.  A value of batteryLow indicates
        that the remaining battery run-time is less than or
        equal to upsConfigLowBattTime.  A value of
        batteryDepleted indicates that the UPS will be unable
        to sustain the present load when and if the utility
        power is lost (including the possibility that the
        utility power is currently absent and the UPS is
        unable to sustain the output).
       | 
    
    
      | upsSecondsOnBattery | 
      .1.3.6.1.2.1.33.1.2.2 | 
    
    
      | 
        If the unit is on battery power, the elapsed time
        since the UPS last switched to battery power, or the
        time since the network management subsystem was last
        restarted, whichever is less.  Zero shall be returned
        if the unit is not on battery power.
       | 
    
    
      | upsEstimatedMinutesRemaining | 
      .1.3.6.1.2.1.33.1.2.3 | 
    
    
      | 
        An estimate of the time to battery charge depletion
        under the present load conditions if the utility power
        is off and remains off, or if it were to be lost and
        remain off.
       | 
    
    
      | upsEstimatedChargeRemaining | 
      .1.3.6.1.2.1.33.1.2.4 | 
    
    
      | 
        An estimate of the battery charge remaining expressed
        as a percent of full charge.
       | 
    
    
      | upsBatteryVoltage | 
      .1.3.6.1.2.1.33.1.2.5 | 
    
    
      | 
        The magnitude of the present battery voltage.
       | 
    
    
      | upsBatteryCurrent | 
      .1.3.6.1.2.1.33.1.2.6 | 
    
    
      | 
        The present battery current.
       | 
    
    
      | upsBatteryTemperature | 
      .1.3.6.1.2.1.33.1.2.7 | 
    
    
      | 
        The ambient temperature at or near the UPS Battery
        casing.
       | 
    
    
      | upsInputLineBads | 
      .1.3.6.1.2.1.33.1.3.1 | 
    
    
      | 
        A count of the number of times the input entered an
        out-of-tolerance condition as defined by the
        manufacturer.  This count is incremented by one each
        time the input transitions from zero out-of-tolerance
        lines to one or more input lines out-of-tolerance.
       | 
    
    
      | upsInputNumLines | 
      .1.3.6.1.2.1.33.1.3.2 | 
    
    
      | 
        The number of input lines utilized in this device.
        This variable indicates the number of rows in the
        input table.
       | 
    
    
      | upsInputEntry | 
      .1.3.6.1.2.1.33.1.3.3.1 | 
    
    
      | 
        An entry containing information applicable to a
        particular input line.
       | 
    
    
      | upsOutputSource | 
      .1.3.6.1.2.1.33.1.4.1 | 
    
    
      | 
        The present source of output power.  The enumeration
        none(2) indicates that there is no source of output
        power (and therefore no output power), for example,
        the system has opened the output breaker.
       | 
    
    
      | upsOutputFrequency | 
      .1.3.6.1.2.1.33.1.4.2 | 
    
    
      | 
        The present output frequency.
       | 
    
    
      | upsOutputNumLines | 
      .1.3.6.1.2.1.33.1.4.3 | 
    
    
      | 
        The number of output lines utilized in this device.
        This variable indicates the number of rows in the
        output table.
       | 
    
    
      | upsOutputEntry | 
      .1.3.6.1.2.1.33.1.4.4.1 | 
    
    
      | 
        An entry containing information applicable to a
        particular output line.
       | 
    
    
      | upsBypassFrequency | 
      .1.3.6.1.2.1.33.1.5.1 | 
    
    
      | 
        The present bypass frequency.
       | 
    
    
      | upsBypassNumLines | 
      .1.3.6.1.2.1.33.1.5.2 | 
    
    
      | 
        The number of bypass lines utilized in this device.
        This entry indicates the number of rows in the bypass
        table.
       | 
    
    
      | upsBypassEntry | 
      .1.3.6.1.2.1.33.1.5.3.1 | 
    
    
      | 
        An entry containing information applicable to a
        particular bypass input.
       | 
    
    
      | upsAlarmsPresent | 
      .1.3.6.1.2.1.33.1.6.1 | 
    
    
      | 
        The present number of active alarm conditions.
       | 
    
    
      | upsAlarmEntry | 
      .1.3.6.1.2.1.33.1.6.2.1 | 
    
    
      | 
        An entry containing information applicable to a
        particular alarm.
       | 
    
    
      | upsTestId | 
      .1.3.6.1.2.1.33.1.7.1 | 
    
    
      | 
        The test is named by an OBJECT IDENTIFIER which
        allows a standard mechanism for the initiation of
        tests, including the well known tests identified in
        this document as well as those introduced by a
        particular implementation, i.e., as documented in the
        private enterprise MIB definition for the device.
        Setting this variable initiates the named test. Sets
        to this variable require the presence of
        upsTestSpinLock in the same SNMP message.
        The set request will be rejected with an appropriate
        error message if the requested test cannot be
        performed, including attempts to start a test when
        another test is already in progress.  The status of
        the current or last test is maintained in
        upsTestResultsSummary. Tests in progress may be
        aborted by setting the upsTestId variable to
        upsTestAbortTestInProgress.
        Read operations return the value of the name of the
        test in progress if a test is in progress or the name
        of the last test performed if no test is in progress,
        unless no test has been run, in which case the well
        known value upsTestNoTestsInitiated is returned.
       | 
    
    
      | upsTestSpinLock | 
      .1.3.6.1.2.1.33.1.7.2 | 
    
    
      | 
        A spin lock on the test subsystem.  The spinlock is
        used as follows.
        Before starting a test, a manager-station should make
        sure that a test is not in progress as follows:
        try_again:
        get (upsTestSpinLock)
        while (upsTestResultsSummary == inProgress) {
        /* loop while a test is running for another
        manager */
        short delay
        get (upsTestSpinLock)
        }
        lock_value = upsTestSpinLock
        /* no test in progress, start the test */
        set (upsTestSpinLock = lock_value, upsTestId =
        requested_test)
        if (error_index == 1) { /* (upsTestSpinLock
        failed) */
        /* if problem is not access control, then
        some other manager slipped in ahead of us
        */
        goto try_again
        }
        if (error_index == 2) { /* (upsTestId) */
        /* cannot perform the test */
        give up
        }
        /* test started ok */
        /* wait for test completion by polling
        upsTestResultsSummary */
        get (upsTestSpinLock, upsTestResultsSummary,
        upsTestResultsDetail)
        while (upsTestResultsSummary == inProgress) {
        short delay
        get (upsTestSpinLock, upsTestResultsSummary,
        upsTestResultsDetail)
        }
        /* when test completes, retrieve any additional
        test results */
        /* if upsTestSpinLock == lock_value + 1, then
        these are our test */
        /* results (as opposed to another manager's */
        The initial value of upsTestSpinLock at agent
        initialization shall
        be 1.
       | 
    
    
      | upsTestResultsSummary | 
      .1.3.6.1.2.1.33.1.7.3 | 
    
    
      | 
        The results of the current or last UPS diagnostics
        test performed.  The values for donePass(1),
        doneWarning(2), and doneError(3) indicate that the
        test completed either successfully, with a warning, or
        with an error, respectively.  The value aborted(4) is
        returned for tests which are aborted by setting the
        value of upsTestId to upsTestAbortTestInProgress.
        Tests which have not yet concluded are indicated by
        inProgress(5).  The value noTestsInitiated(6)
        indicates that no previous test results are available,
        such as is the case when no tests have been run since
        the last reinitialization of the network management
        subsystem and the system has no provision for non-
        volatile storage of test results.
       | 
    
    
      | upsTestResultsDetail | 
      .1.3.6.1.2.1.33.1.7.4 | 
    
    
      | 
        Additional information about upsTestResultsSummary.
        If no additional information available, a zero length
        string is returned.
       | 
    
    
      | upsTestStartTime | 
      .1.3.6.1.2.1.33.1.7.5 | 
    
    
      | 
        The value of sysUpTime at the time the test in
        progress was initiated, or, if no test is in progress,
        the time the previous test was initiated.  If the
        value of upsTestResultsSummary is noTestsInitiated(6),
        upsTestStartTime has the value 0.
       | 
    
    
      | upsTestElapsedTime | 
      .1.3.6.1.2.1.33.1.7.6 | 
    
    
      | 
        The amount of time, in TimeTicks, since the test in
        progress was initiated, or, if no test is in progress,
        the previous test took to complete.  If the value of
        upsTestResultsSummary is noTestsInitiated(6),
        upsTestElapsedTime has the value 0.
       | 
    
    
      | upsShutdownType | 
      .1.3.6.1.2.1.33.1.8.1 | 
    
    
      | 
        This object determines the nature of the action to be
        taken at the time when the countdown of the
        upsShutdownAfterDelay and upsRebootWithDuration
        objects reaches zero.
        Setting this object to output(1) indicates that
        shutdown requests should cause only the output of the
        UPS to turn off.  Setting this object to system(2)
        indicates that shutdown requests will cause the entire
        UPS system to turn off.
       | 
    
    
      | upsShutdownAfterDelay | 
      .1.3.6.1.2.1.33.1.8.2 | 
    
    
      | 
        Setting this object will shutdown (i.e., turn off)
        either the UPS output or the UPS system (as determined
        by the value of upsShutdownType at the time of
        shutdown) after the indicated number of seconds, or
        less if the UPS batteries become depleted. Setting
        this object to 0 will cause the shutdown to occur
        immediately.  Setting this object to -1 will abort the
        countdown.  If the system is already in the desired
        state at the time the countdown reaches 0, then
        nothing will happen.  That is, there is no additional
        action at that time if upsShutdownType = system and
        the system is already off.  Similarly, there is no
        additional action at that time if upsShutdownType =
        output and the output is already off.  When read,
        upsShutdownAfterDelay will return the number of
        seconds remaining until shutdown, or -1 if no shutdown
        countdown is in effect.  On some systems, if the agent
        is restarted while a shutdown countdown is in effect,
        the countdown may be aborted.  Sets to this object
        override any upsShutdownAfterDelay already in effect.
       | 
    
    
      | upsStartupAfterDelay | 
      .1.3.6.1.2.1.33.1.8.3 | 
    
    
      | 
        Setting this object will start the output after the
        indicated number of seconds, including starting the
        UPS, if necessary.  Setting this object to 0 will
        cause the startup to occur immediately.  Setting this
        object to -1 will abort the countdown.  If the output
        is already on at the time the countdown reaches 0,
        then nothing will happen.  Sets to this object
        override the effect of any upsStartupAfterDelay
        countdown or upsRebootWithDuration countdown in
        progress.  When read, upsStartupAfterDelay will return
        the number of seconds until startup, or -1 if no
        startup countdown is in effect.  If the countdown
        expires during a utility failure, the startup shall
        not occur until the utility power is restored.  On
        some systems, if the agent is restarted while a
        startup countdown is in effect, the countdown is
        aborted.
       | 
    
    
      | upsRebootWithDuration | 
      .1.3.6.1.2.1.33.1.8.4 | 
    
    
      | 
        Setting this object will immediately shutdown (i.e.,
        turn off) either the UPS output or the UPS system (as
        determined by the value of upsShutdownType at the time
        of shutdown) for a period equal to the indicated
        number of seconds, after which time the output will be
        started, including starting the UPS, if necessary.  If
        the number of seconds required to perform the request
        is greater than the requested duration, then the
        requested shutdown and startup cycle shall be
        performed in the minimum time possible, but in no case
        shall this require more than the requested duration
        plus 60 seconds.  When read, upsRebootWithDuration
        shall return the number of seconds remaining in the
        countdown, or -1 if no countdown is in progress.  If
        the startup should occur during a utility failure, the
        startup shall not occur until the utility power is
        restored.
       | 
    
    
      | upsAutoRestart | 
      .1.3.6.1.2.1.33.1.8.5 | 
    
    
      | 
        Setting this object to 'on' will cause the UPS system
        to restart after a shutdown if the shutdown occurred
        during a power loss as a result of either a
        upsShutdownAfterDelay or an internal battery depleted
        condition.  Setting this object to 'off' will prevent
        the UPS system from restarting after a shutdown until
        an operator manually or remotely explicitly restarts
        it.  If the UPS is in a startup or reboot countdown,
        then the UPS will not restart until that delay has
        been satisfied.
       | 
    
    
      | upsConfigInputVoltage | 
      .1.3.6.1.2.1.33.1.9.1 | 
    
    
      | 
        The magnitude of the nominal input voltage.  On those
        systems which support read-write access to this
        object, if there is an attempt to set this variable to
        a value that is not supported, the request must be
        rejected and the agent shall respond with an
        appropriate error message, i.e., badValue for SNMPv1,
        or inconsistentValue for SNMPv2.
       | 
    
    
      | upsConfigInputFreq | 
      .1.3.6.1.2.1.33.1.9.2 | 
    
    
      | 
        The nominal input frequency.  On those systems which
        support read-write access to this object, if there is
        an attempt to set this variable to a value that is not
        supported, the request must be rejected and the agent
        shall respond with an appropriate error message, i.e.,
        badValue for SNMPv1, or inconsistentValue for SNMPv2.
       | 
    
    
      | upsConfigOutputVoltage | 
      .1.3.6.1.2.1.33.1.9.3 | 
    
    
      | 
        The magnitude of the nominal output voltage.  On
        those systems which support read-write access to this
        object, if there is an attempt to set this variable to
        a value that is not supported, the request must be
        rejected and the agent shall respond with an
        appropriate error message, i.e., badValue for SNMPv1,
        or inconsistentValue for SNMPv2.
       | 
    
    
      | upsConfigOutputFreq | 
      .1.3.6.1.2.1.33.1.9.4 | 
    
    
      | 
        The nominal output frequency.  On those systems which
        support read-write access to this object, if there is
        an attempt to set this variable to a value that is not
        supported, the request must be rejected and the agent
        shall respond with an appropriate error message, i.e.,
        badValue for SNMPv1, or inconsistentValue for SNMPv2.
       | 
    
    
      | upsConfigOutputVA | 
      .1.3.6.1.2.1.33.1.9.5 | 
    
    
      | 
        The magnitude of the nominal Volt-Amp rating.
       | 
    
    
      | upsConfigOutputPower | 
      .1.3.6.1.2.1.33.1.9.6 | 
    
    
      | 
        The magnitude of the nominal true power rating.
       | 
    
    
      | upsConfigLowBattTime | 
      .1.3.6.1.2.1.33.1.9.7 | 
    
    
      | 
        The value of upsEstimatedMinutesRemaining at which a
        lowBattery condition is declared.  For agents which
        support only discrete (discontinuous) values, then the
        agent shall round up to the next supported value.  If
        the requested value is larger than the largest
        supported value, then the largest supported value
        shall be selected.
       | 
    
    
      | upsConfigAudibleStatus | 
      .1.3.6.1.2.1.33.1.9.8 | 
    
    
      | 
        The requested state of the audible alarm.  When in
        the disabled state, the audible alarm should never
        sound.  The enabled state is self-describing.  Setting
        this object to muted(3) when the audible alarm is
        sounding shall temporarily silence the alarm.  It will
        remain muted until it would normally stop sounding and
        the value returned for read operations during this
        period shall equal muted(3).  At the end of this
        period, the value shall revert to enabled(2).  Writes
        of the value muted(3) when the audible alarm is not
        sounding shall be accepted but otherwise shall have no
        effect.
       | 
    
    
      | upsConfigLowVoltageTransferPoint | 
      .1.3.6.1.2.1.33.1.9.9 | 
    
    
      | 
        The minimum input line voltage allowed before the UPS
        system transfers to battery backup.
       | 
    
    
      | upsConfigHighVoltageTransferPoint | 
      .1.3.6.1.2.1.33.1.9.10 | 
    
    
      | 
        The maximum line voltage allowed before the UPS
        system transfers to battery backup.
       | 
    
  
  
    
      | upsMIB | 
      .1.3.6.1.2.1.33 | 
    
    
      | 
        The MIB module to describe Uninterruptible Power
        Supplies.
       | 
    
    
      | upsObjects | 
      .1.3.6.1.2.1.33.1 | 
    
    
      | upsIdent | 
      .1.3.6.1.2.1.33.1.1 | 
    
    
      | upsBattery | 
      .1.3.6.1.2.1.33.1.2 | 
    
    
      | upsInput | 
      .1.3.6.1.2.1.33.1.3 | 
    
    
      | upsOutput | 
      .1.3.6.1.2.1.33.1.4 | 
    
    
      | upsBypass | 
      .1.3.6.1.2.1.33.1.5 | 
    
    
      | upsAlarm | 
      .1.3.6.1.2.1.33.1.6 | 
    
    
      | upsWellKnownAlarms | 
      .1.3.6.1.2.1.33.1.6.3 | 
    
    
      | upsAlarmBatteryBad | 
      .1.3.6.1.2.1.33.1.6.3.1 | 
    
    
      | 
        One or more batteries have been determined to require
        replacement.
       | 
    
    
      | upsAlarmOnBattery | 
      .1.3.6.1.2.1.33.1.6.3.2 | 
    
    
      | 
        The UPS is drawing power from the batteries.
       | 
    
    
      | upsAlarmLowBattery | 
      .1.3.6.1.2.1.33.1.6.3.3 | 
    
    
      | 
        The remaining battery run-time is less than or equal
        to upsConfigLowBattTime.
       | 
    
    
      | upsAlarmDepletedBattery | 
      .1.3.6.1.2.1.33.1.6.3.4 | 
    
    
      | 
        The UPS will be unable to sustain the present load
        when and if the utility power is lost.
       | 
    
    
      | upsAlarmTempBad | 
      .1.3.6.1.2.1.33.1.6.3.5 | 
    
    
      | 
        A temperature is out of tolerance.
       | 
    
    
      | upsAlarmInputBad | 
      .1.3.6.1.2.1.33.1.6.3.6 | 
    
    
      | 
        An input condition is out of tolerance.
       | 
    
    
      | upsAlarmOutputBad | 
      .1.3.6.1.2.1.33.1.6.3.7 | 
    
    
      | 
        An output condition (other than OutputOverload) is
        out of tolerance.
       | 
    
    
      | upsAlarmOutputOverload | 
      .1.3.6.1.2.1.33.1.6.3.8 | 
    
    
      | 
        The output load exceeds the UPS output capacity.
       | 
    
    
      | upsAlarmOnBypass | 
      .1.3.6.1.2.1.33.1.6.3.9 | 
    
    
      | 
        The Bypass is presently engaged on the UPS.
       | 
    
    
      | upsAlarmBypassBad | 
      .1.3.6.1.2.1.33.1.6.3.10 | 
    
    
      | 
        The Bypass is out of tolerance.
       | 
    
    
      | upsAlarmOutputOffAsRequested | 
      .1.3.6.1.2.1.33.1.6.3.11 | 
    
    
      | 
        The UPS has shutdown as requested, i.e., the output
        is off.
       | 
    
    
      | upsAlarmUpsOffAsRequested | 
      .1.3.6.1.2.1.33.1.6.3.12 | 
    
    
      | 
        The entire UPS has shutdown as commanded.
       | 
    
    
      | upsAlarmChargerFailed | 
      .1.3.6.1.2.1.33.1.6.3.13 | 
    
    
      | 
        An uncorrected problem has been detected within the
        UPS charger subsystem.
       | 
    
    
      | upsAlarmUpsOutputOff | 
      .1.3.6.1.2.1.33.1.6.3.14 | 
    
    
      | 
        The output of the UPS is in the off state.
       | 
    
    
      | upsAlarmUpsSystemOff | 
      .1.3.6.1.2.1.33.1.6.3.15 | 
    
    
      | 
        The UPS system is in the off state.
       | 
    
    
      | upsAlarmFanFailure | 
      .1.3.6.1.2.1.33.1.6.3.16 | 
    
    
      | 
        The failure of one or more fans in the UPS has been
        detected.
       | 
    
    
      | upsAlarmFuseFailure | 
      .1.3.6.1.2.1.33.1.6.3.17 | 
    
    
      | 
        The failure of one or more fuses has been detected.
       | 
    
    
      | upsAlarmGeneralFault | 
      .1.3.6.1.2.1.33.1.6.3.18 | 
    
    
      | 
        A general fault in the UPS has been detected.
       | 
    
    
      | upsAlarmDiagnosticTestFailed | 
      .1.3.6.1.2.1.33.1.6.3.19 | 
    
    
      | 
        The result of the last diagnostic test indicates a
        failure.
       | 
    
    
      | upsAlarmCommunicationsLost | 
      .1.3.6.1.2.1.33.1.6.3.20 | 
    
    
      | 
        A problem has been encountered in the communications
        between the agent and the UPS.
       | 
    
    
      | upsAlarmAwaitingPower | 
      .1.3.6.1.2.1.33.1.6.3.21 | 
    
    
      | 
        The UPS output is off and the UPS is awaiting the
        return of input power.
       | 
    
    
      | upsAlarmShutdownPending | 
      .1.3.6.1.2.1.33.1.6.3.22 | 
    
    
      | 
        A upsShutdownAfterDelay countdown is underway.
       | 
    
    
      | upsAlarmShutdownImminent | 
      .1.3.6.1.2.1.33.1.6.3.23 | 
    
    
      | 
        The UPS will turn off power to the load in less than
        5 seconds; this may be either a timed shutdown or a
        low battery shutdown.
       | 
    
    
      | upsAlarmTestInProgress | 
      .1.3.6.1.2.1.33.1.6.3.24 | 
    
    
      | 
        A test is in progress, as initiated and indicated by
        the Test Group.  Tests initiated via other
        implementation-specific mechanisms can indicate the
        presence of the testing in the alarm table, if
        desired, via a OBJECT-IDENTITY macro in the MIB
        document specific to that implementation and are
        outside the scope of this OBJECT-IDENTITY.
       | 
    
    
      | upsTest | 
      .1.3.6.1.2.1.33.1.7 | 
    
    
      | upsWellKnownTests | 
      .1.3.6.1.2.1.33.1.7.7 | 
    
    
      | upsTestNoTestsInitiated | 
      .1.3.6.1.2.1.33.1.7.7.1 | 
    
    
      | 
        No tests have been initiated and no test is in
        progress.
       | 
    
    
      | upsTestAbortTestInProgress | 
      .1.3.6.1.2.1.33.1.7.7.2 | 
    
    
      | 
        The test in progress is to be aborted / the test in
        progress was aborted.
       | 
    
    
      | upsTestGeneralSystemsTest | 
      .1.3.6.1.2.1.33.1.7.7.3 | 
    
    
      | 
        The manufacturer's standard test of UPS device
        systems.
       | 
    
    
      | upsTestQuickBatteryTest | 
      .1.3.6.1.2.1.33.1.7.7.4 | 
    
    
      | 
        A test that is sufficient to determine if the battery
        needs replacement.
       | 
    
    
      | upsTestDeepBatteryCalibration | 
      .1.3.6.1.2.1.33.1.7.7.5 | 
    
    
      | 
        The system is placed on battery to a discharge level,
        set by the manufacturer, sufficient to determine
        battery replacement and battery run-time with a high
        degree of confidence.  WARNING:  this test will leave
        the battery in a low charge state and will require
        time for recharging to a level sufficient to provide
        normal battery duration for the protected load.
       | 
    
    
      | upsControl | 
      .1.3.6.1.2.1.33.1.8 | 
    
    
      | upsConfig | 
      .1.3.6.1.2.1.33.1.9 | 
    
    
      | upsTraps | 
      .1.3.6.1.2.1.33.2 | 
    
    
      | upsConformance | 
      .1.3.6.1.2.1.33.3 | 
    
    
      | upsCompliances | 
      .1.3.6.1.2.1.33.3.1 | 
    
    
      | upsGroups | 
      .1.3.6.1.2.1.33.3.2 | 
    
    
      | upsSubsetGroups | 
      .1.3.6.1.2.1.33.3.2.1 | 
    
    
      | upsBasicGroups | 
      .1.3.6.1.2.1.33.3.2.2 | 
    
    
      | upsFullGroups | 
      .1.3.6.1.2.1.33.3.2.3 | 
    
  
  
    
      | upsSubsetIdentGroup | 
      .1.3.6.1.2.1.33.3.2.1.1 | 
    
    
      | 
        The upsSubsetIdentGroup defines objects which are
        common across all UPSs which meet subset compliance.
        Most devices which conform to the upsSubsetIdentGroup
        will provide access to these objects via a proxy
        agent.  If the proxy agent is compatible with multiple
        UPS types, configuration of the proxy agent will
        require specifying some of these values, either
        individually, or as a group (perhaps through a table
        lookup mechanism based on the UPS model number).
       | 
    
    
      | upsSubsetBatteryGroup | 
      .1.3.6.1.2.1.33.3.2.1.2 | 
    
    
      | 
        The upsSubsetBatteryGroup defines the objects that
        are common to battery groups of two-contact UPSs.
       | 
    
    
      | upsSubsetInputGroup | 
      .1.3.6.1.2.1.33.3.2.1.3 | 
    
    
      | 
        The upsSubsetInputGroup defines the objects that are
        common to the Input groups of two-contact UPSs.
       | 
    
    
      | upsSubsetOutputGroup | 
      .1.3.6.1.2.1.33.3.2.1.4 | 
    
    
      | 
        The upsSubsetOutputGroup defines the objects that are
        common to the Output groups of two-contact UPSs.
       | 
    
    
      | upsSubsetAlarmGroup | 
      .1.3.6.1.2.1.33.3.2.1.6 | 
    
    
      | 
        The upsSubsetAlarmGroup defines the objects that are
        common to the Alarm groups of two-contact UPSs.
       | 
    
    
      | upsSubsetControlGroup | 
      .1.3.6.1.2.1.33.3.2.1.8 | 
    
    
      | 
        The upsSubsetControlGroup defines the objects that
        are common to the Control groups of two-contact UPSs.
       | 
    
    
      | upsSubsetConfigGroup | 
      .1.3.6.1.2.1.33.3.2.1.9 | 
    
    
      | 
        The upsSubsetConfigGroup defines the objects that are
        common to the Config groups of two-contact UPSs.
       | 
    
    
      | upsBasicIdentGroup | 
      .1.3.6.1.2.1.33.3.2.2.1 | 
    
    
      | 
        The upsBasicIdentGroup defines objects which are
        common to the Ident group of compliant UPSs which
        support basic functions.
       | 
    
    
      | upsBasicBatteryGroup | 
      .1.3.6.1.2.1.33.3.2.2.2 | 
    
    
      | 
        The upsBasicBatteryGroup defines the objects that are
        common to the battery groups of compliant UPSs which
        support basic functions.
       | 
    
    
      | upsBasicInputGroup | 
      .1.3.6.1.2.1.33.3.2.2.3 | 
    
    
      | 
        The upsBasicInputGroup defines the objects that are
        common to the Input groups of compliant UPSs which
        support basic functions.
       | 
    
    
      | upsBasicOutputGroup | 
      .1.3.6.1.2.1.33.3.2.2.4 | 
    
    
      | 
        The upsBasicOutputGroup defines the objects that are
        common to the Output groups of compliant UPSs which
        support basic functions.
       | 
    
    
      | upsBasicAlarmGroup | 
      .1.3.6.1.2.1.33.3.2.2.6 | 
    
    
      | 
        The upsBasicAlarmGroup defines the objects that are
        common to the Alarm  groups of compliant UPSs which
        support basic functions.
       | 
    
    
      | upsBasicTestGroup | 
      .1.3.6.1.2.1.33.3.2.2.7 | 
    
    
      | 
        The upsBasicTestGroup defines the objects that are
        common to the Test groups of compliant UPSs which
        support basic functions.
       | 
    
    
      | upsBasicControlGroup | 
      .1.3.6.1.2.1.33.3.2.2.8 | 
    
    
      | 
        The upsBasicControlGroup defines the objects that are
        common to the Control groups of compliant UPSs which
        support basic functions.
       | 
    
    
      | upsBasicConfigGroup | 
      .1.3.6.1.2.1.33.3.2.2.9 | 
    
    
      | 
        The upsBasicConfigGroup defines the objects that are
        common to the Config groups of UPSs which support
        basic functions.
       | 
    
    
      | upsBasicBypassGroup | 
      .1.3.6.1.2.1.33.3.2.2.5 | 
    
    
      | 
        The upsBasicBypassGroup defines the objects that are
        common to the Bypass groups of compliant UPSs which
        support basic functions.
       | 
    
    
      | upsFullIdentGroup | 
      .1.3.6.1.2.1.33.3.2.3.1 | 
    
    
      | 
        The upsFullIdentGroup defines objects which are
        common to the Ident group of fully compliant UPSs.
       | 
    
    
      | upsFullBatteryGroup | 
      .1.3.6.1.2.1.33.3.2.3.2 | 
    
    
      | 
        The upsFullBatteryGroup defines the objects that are
        common to the battery groups of fully compliant UPSs.
       | 
    
    
      | upsFullInputGroup | 
      .1.3.6.1.2.1.33.3.2.3.3 | 
    
    
      | 
        The upsFullInputGroup defines the objects that are
        common to the Input groups of fully compliant UPSs.
       | 
    
    
      | upsFullOutputGroup | 
      .1.3.6.1.2.1.33.3.2.3.4 | 
    
    
      | 
        The upsFullOutputGroup defines the objects that are
        common to the Output groups of fully compliant UPSs.
       | 
    
    
      | upsFullAlarmGroup | 
      .1.3.6.1.2.1.33.3.2.3.6 | 
    
    
      | 
        The upsFullAlarmGroup defines the objects that are
        common to the Alarm  groups of fully compliant UPSs.
       | 
    
    
      | upsFullTestGroup | 
      .1.3.6.1.2.1.33.3.2.3.7 | 
    
    
      | 
        The upsFullTestGroup defines the objects that are
        common to the Test groups of fully compliant UPSs.
       | 
    
    
      | upsFullControlGroup | 
      .1.3.6.1.2.1.33.3.2.3.8 | 
    
    
      | 
        The upsFullControlGroup defines the objects that are
        common to the Control groups of fully compliant UPSs.
       | 
    
    
      | upsFullConfigGroup | 
      .1.3.6.1.2.1.33.3.2.3.9 | 
    
    
      | 
        The upsFullConfigGroup defines the objects that are
        common to the Config groups of fully compliant UPSs.
       | 
    
    
      | upsFullBypassGroup | 
      .1.3.6.1.2.1.33.3.2.3.5 | 
    
    
      | 
        The upsFullBypassGroup defines the objects that are
        common to the Bypass groups of fully compliant UPSs.
       |